Changeover from STRUC V4.x to D7-SYS
System- and communication configuring D7-SYS - SIMADYN D
4-31
Edition 03.2001
4.6.5 Test and start-up
Your software is tested and commissioned in Version 3.1x using the CFC
editor which in this case, has a test mode.
in STRUC V.4.x
in D7-SYS
Start IBS G (start-up
program)
Start the CFC editor; in the SIMATIC Manager:
Double click on a CFC chart of the CPU to be tested.
Establish an online
connection to the
CPUs
(IBS G online start)
Changeover into the CFC test mode; in CFC:
In the creation mode, select the menu command
Test >
Test mode
.
Note: This step must be executed for each CPU which
you wish to test.
Interrupt the online
connection to the
CPUs
(IBS G online stop)
Changeover into the creation mode of the CFC; in the
CFC:
Select, in the test mode, the menu command
Test >
Test mode
.
Display the
connector values
online
In the CFC test mode:
Select the connections to be displayed or function blocks
and select the menu command
Test > Log-on
connections
.
Select the
Test > Monitor
menu command to display the
actual values of all these connections, logged-on with
this CPU, online.
Create the
interconnections
online
In the CFC test mode:
Click on the output of the function block which is to be
the source for the interconnection. Then click on the
input which is the destination of the connection.
Delete the
interconnections
online
In the CFC test mode:
Click on the function block input, which is the end of the
interconnection and then select the menu command
Edit
> Delete
.
Insert the function
blocks online
In the CFC test mode:
Select the menu command
View > Catalog
to display
the function block catalog of the CFC.
Select the required function block and drag it, with the
mouse key depressed, to the work area of a CFC chart.
Delete the function
blocks online
In the CFC test mode:
Remove all interconnections which go from the outputs
to the function blocks to be deleted.
Select the function block(s) to be deleted and select the
menu command Edit > Delete.
Differentiation
between temporary
and permanent
online changes (IBS
G OPTIONS as well
as changing the
"permanent" option in
the dialog window
"change value").
All online changes are permanently stored in the CFC, i.
e. they are saved in the CPU change memory. Even
after a CPU has been reset, the executed CPU program
and the CFC charts, which were changed online,
coincide.
Display the error
fields in the "Service
IBS" tool
System diagnostics: Display the error fields of a CPU.
In the CFC:
Select the menu command Target system > Module
status and then change to the register side "Error fields".