Planning
Acoustic and optical configuration
4
27 | 56
Building Technologies
A6V10320094_m_en_--
Fire Safety
2017-10-31
4.5.2 DBS729 optical signals
No.
Flash type
Flashing
frequency
Pulse pattern
Luminous intensity at 32 V,
angle-dependent (typ.)
Standard / Notes
0
Flash
0.8 Hz
Normal
—
1
Flash
0.8 Hz
Normal
Monitoring function
1
2
Alternating
2
0.8 Hz
Normal
—
3
Flash
0.8 Hz
Dark
—
4
Flash
0.8 Hz
Bright
—
5
Flash
0.8 Hz
Bright
Monitoring function
1
6
Alternating
2
0.8 Hz
Bright
—
7
Reserve
—
—
—
—
1
Supervision function: The LEDs are activated once approx. every 4.5 hours and
flash 4 times in succession.
2
In alternating mode, only half of the LEDs flash. After a pause of 50 ms the
other half flash.
See also
2
Optical beam characteristics of interbase DBS729
20 ms
1.25 s
20 ms
1.25 s
10 ms 10 ms
1.25 s
5 ms
1.25 s
35 ms
1.25 s
35 ms
1.25 s
17.5 ms
17.5 ms
1.25 s