Structure and function
Overview of DBS721
3
14 | 56
Building Technologies
A6V10320094_m_en_--
Fire Safety
2017-10-31
3 Structure and function
3.1 Overview of DBS721
Figure 1: View of the DBS721
The sounder interbase DBS721 provides an acoustic alarm in addressed fire
detection systems FS720 and FC360.
The sounder interbase DBS721 can be activated by any point detector via the
control panel.
The loud sound of the interbase can be clearly recognized as a danger signal in
the event of a fire alarm.
11 tones are programmed in the interbase.
Two alarm levels can be activated for different events
(e.g., alarm and evacuation).
If a point detector is not used, the blanking plate BP720 (accessory) can be fitted
on the interbase.
Features
Addressable on the C-NET detector loop
Communication with the control panel via the detector loop
Supply via detector loop
Compatible with all addressable detector bases from the 'Cerberus PRO'
product line
Compatible with all addressable point detectors from the 'Cerberus PRO'
product line
Integrated line separation function
Self test function
Yellow LED in interbase to indicate servicing required
Synchronization of sounds with all alarm sounders, interbases and audible
bases on the same detector loop
No additional detector base required