9
en
Technical data
DE 1821515
DE 5151821
DE 2427515
DE 5152427
Rated output
[kW]
18
21
24
27
Rated voltage
[V]
400
400
Fuse protection
[A]
32
40
Minimum conductor cross-section
[mm
2
]
4
6
Warm water flow at rated output
with temperature increase from
12 °C to 38 °C
[l/min]
9.9
11.6
13.2
13.9
12 °C to 60 °C
[l/min]
5.4
6.3
7.2
7.6
Start-up flow
[l/min]
2.6
2.6
Start-up flow pressure *
[MPa (bar)]
0.025 (0.25)
0.025 (0.25)
Application area in water
specific electric resistance at 15 °C
[Ωcm]
≥ 1 300
≥ 1 300
Rated pressure
[MPa (bar)]
1.0 (10.0)
1.0 (10.0)
Maximum permissible supply temperature
[°C]
55
55
Maximum mains impedance at connection point
[Ω]
≤ 0.44
≤ 0.244
* The pressure loss on the mixer must also be added
Operation with prewarmed water (solar heated)
The continuous-flow heater can only heat prewarmed water
to a max. of 60 °C. If the cold water supply exceeds a tem-
perature of 55 °C, the water will not be warmed any further.
Important:
The cold water supply temperature must not be
higher than 55 °!
If the cold water supply exceeds a temperature of 60 °C, a
circuit breaker will trigger and shut the appliance off. There-
fore, the residential plumbing must be equipped with a ther-
mostatic premixer (e. g. special accessory
BZ 45T20
) that will
limit the cold water supply temperature to a max. of 55 ° by
appropriately mixing in cold water.
VI.
Startup/additional information
The device is compliant to IEC 61000-3-12.
First start-up
Switch on the fuses.
■
Setting the temperature.
■
Starts rinsing: Open the warm water tap and allow water
■
to flow for at least 1 minute (flow-rate at least 6 litres per
minute). Only then (for safety reasons) will the appliance
begin to heat.
Tip:
Should the appliance not start because of a reduced
flow-rate, remove the perlator, shower head or similar before
start and repeat the process.
Remove the flow-rate limiter (see Fig. A) with low water
■
pressure.
Explain the operation of the continuous-flow heater to
■
the user.
A
If the continuous-flow heater does not have sufficient
water flow due to low water line pressure in your do-
mestic plumbing system, remove the flow-rate
limiter.
B
Priority circuit for the combination with electrical
storage heaters:
For operation with a priority circuit, a special load
shedding relay BZ 45L20 (special accessory) is re-
quired. Other existing load shedding relays, with the
exception of electronic load shedding relays, may
malfunction.
C
The control electronics must be coded when operated
with a load shedding relay.
Summary of Contents for DE 1821515
Page 7: ...7 de 07 12 ...
Page 20: ...20 ...
Page 21: ......
Page 23: ...II ca 72 388 ca 96 70 44 100 332 8 b c 7 b c 6 a b c 5 4B 4A 2 3 hot cold 100 1 A B ...
Page 24: ...III 2A 2B a 3 1 5 4 1 2 3 max 16 mm B ca 2 mm A ...
Page 27: ...A 1 2 3 4 L 3 L 2 L 1 3 2 1 PE PE B C ...
Page 28: ......
Page 47: ...07 12 ...