Siemens Building Technologies

CA2N3295E / 03.1999

Landis & Staefa Division

1/4

3

295

DESIGO 30

Service terminal

BCS

Hand-held terminal with three operating levels, easy-to-read display panel and
user-friendly key pad, for commissioning, tuning and servicing of HVAC systems
incorporating controllers in the DESIGO 30 range.

The service terminal is connected to the LON bus, so allowing the user access
(depending on operating level) to the data from the connected DESIGO 30 devices.

The basic procedure for operation is as follows:
Menu and data points are selected using the four navigation keys. Selected points are
displayed in inverse video, and adjustable values can be modified with the  + and  
keys. Modified values are accepted with  enter , and functions are terminated with the
esc  key.

50169A

?

esc

+

1

2

3

4

Key
1 Display
2 Info key
3 Edit keys
4 Navigation keys

Operating level 1:

(level on start-up): For access to all the controller values needed
for normal operation (plant status, all inputs and outputs, set-
points and time programmes). Simple commissioning using the
check lists.

Operating level 2:

Controller tuning based on the check list.

Operating level 3:

Access to all controller data (for specially trained service
engineers and system contractors).

Factory settings:
–  Operating level 1  =  A
–  Operating level 2  =  B
–  Operating level 3  =  C

Use / Functions

Operating levels

Password

Summary of Contents for DESIGIO 30

Page 1: ...tion keys Selected points are displayed in inverse video and adjustable values can be modified with the and keys Modified values are accepted with enter and functions are terminated with the esc key 50169A esc 1 2 3 4 Key 1 Display 2 Info key 3 Edit keys 4 Navigation keys Operating level 1 level on start up For access to all the controller values needed for normal operation plant status all inputs...

Page 2: ...eek program Date program Proportional seq Y1 Proportional seq Y3 Proportional seq Y5 Value of cascade Setpoint reset Regulation sensor X1 Shift sensor X2 Setpoint External Output Heating Y1 Output Cooling Y3 Output heat Y5 Output Digital Y2 Alarm Output Clock Frost sensor X4 Output Frost Control relay Step 1 Control relay Step 2 Structure data Alarm summaries Device data Internal setting Overview ...

Page 3: ...e bus and for password entry 50505Aen X1 21 0 C X2 14 0 C X3 23 0 C X4 10 0 C Y1 5 3V Y3 0 0V FRIND On Y2 0 0V Ventilation East Important datapoints YD1 On YD2 Off CLCK Auto I W 20 0 C MODE Auto XB 5 0 C XON 5 0 C FCOF 1 0K Modifying a value Use the navigation keys to select the value If modi fiable the value will be displayed in inverse video Prepare to modify value by pressing The value will fla...

Page 4: ... comms and power LON with BACnet protocol Connection 2 wire comms only without AC 24 V Max cable length 1100 m unscreened Bus termination On rear set by switch Weight excluding packaging 0 38 kg Dimensions W x H x D 110 x 210 x 45 mm Cleaning Use a damp cloth only Use soap or solvent only Do not allow moisture to enter the housing Conditions of use For indoor use Temperature range Operation 5 45 C...

Reviews: