CA2N3295E / 03.1999

Siemens Building Technologies

4/4

Landis & Staefa Division

V

50507EN

8

-30

4

0

K

30

 Ventilation East

Proportional sequence Y1

K

2

2

50508EN

-10

32

°C

25

2

 Ventilation East

Setpoint reset

Changing a value on the graph:
Select the value with the navigation keys. If it is
modifiable, the value will be shown in inverse video.
Prepare the modification with + /  . The value will
flash. Modify the value with the + / – keys.
Press enter to adopt the new value, or press esc to
abandon it (the original value will be retained).

Supply voltage 

Low voltage (SELV)

Nominal voltage

AC 24 V, 50/60 Hz

–  Admissible tolerance

+15 / –10  %

Power consumption

Max. 200 mA

Connection

RJ45 socket

Service cable

3 m, RJ45 connector at each end (comms and power)

LON with BACnet protocol

–  Connection

2-wire (comms only, without AC 24 V)

–  Max. cable length

1100 m (unscreened)

–  Bus termination

On rear, set by switch

Weight  (excluding packaging)

0.38 kg

Dimensions (W x H x D)

110 x 210 x 45 mm

Cleaning

Use a damp cloth only. Use soap or solvent only. 
Do not allow moisture to enter the housing.

Conditions of use 

For indoor use

Temperature range

–  Operation

    5 ... 45 °C

–  Storage

–25 ... 70 °C

Ambient humidity

10 ... 90 %rh, non-condensing

Product safety

EN 61010-1

–  Overvoltage category

II

–  Contamination level

2

Electrical safety

SELV-E (PELV to IEC 364-4-41)

Conformity

This product meets the requirements for CE marking

V

E

D

All dimensions in mm

5061 1

110

21

0

45

50612

85

13

0

47

Graphics

Technical data

Power supply

Connection

Communication

Weight / Dimensions

Cleaning

General ambient conditions

Safety

Dimensions

 1999 Siemens Building Technologies Ltd.

Replaces R21-07.50

Wall bracket

Summary of Contents for DESIGIO 30

Page 1: ...tion keys Selected points are displayed in inverse video and adjustable values can be modified with the and keys Modified values are accepted with enter and functions are terminated with the esc key 50169A esc 1 2 3 4 Key 1 Display 2 Info key 3 Edit keys 4 Navigation keys Operating level 1 level on start up For access to all the controller values needed for normal operation plant status all inputs...

Page 2: ...eek program Date program Proportional seq Y1 Proportional seq Y3 Proportional seq Y5 Value of cascade Setpoint reset Regulation sensor X1 Shift sensor X2 Setpoint External Output Heating Y1 Output Cooling Y3 Output heat Y5 Output Digital Y2 Alarm Output Clock Frost sensor X4 Output Frost Control relay Step 1 Control relay Step 2 Structure data Alarm summaries Device data Internal setting Overview ...

Page 3: ...e bus and for password entry 50505Aen X1 21 0 C X2 14 0 C X3 23 0 C X4 10 0 C Y1 5 3V Y3 0 0V FRIND On Y2 0 0V Ventilation East Important datapoints YD1 On YD2 Off CLCK Auto I W 20 0 C MODE Auto XB 5 0 C XON 5 0 C FCOF 1 0K Modifying a value Use the navigation keys to select the value If modi fiable the value will be displayed in inverse video Prepare to modify value by pressing The value will fla...

Page 4: ... comms and power LON with BACnet protocol Connection 2 wire comms only without AC 24 V Max cable length 1100 m unscreened Bus termination On rear set by switch Weight excluding packaging 0 38 kg Dimensions W x H x D 110 x 210 x 45 mm Cleaning Use a damp cloth only Use soap or solvent only Do not allow moisture to enter the housing Conditions of use For indoor use Temperature range Operation 5 45 C...

Reviews: