Features 

Compact series 
The compact build allows direct mounting on the damper shaft. 

Plug-in terminal blocks 
Plug-in terminal blocks for easy exchange of room automation stations. 

Integrated actuator 
The actuator gear base is integrated into the housing of the actuating DXR. It supports 

dampers with up to 10 Nm torque.  

  

Use 

The Desigo Room Automation offers the highest level of flexibility for energy-optimized 

solutions while satisfying requirements for temperature control, ventilation and comfort using 

standard tools and established workflows. 

Pre-installed application types 
Variable (VAV) and constant air volume flow control 

  

Functions 

The selected application and its parameters as well as input and output configuration 

determine the room automation station’s functionality.

 

A detailed description of functionality is available in the ABT (Automation Building Tool) 

online help. 

Communication 

  2-port Ethernet switch for cost-effective cabling via line topology 

  USB connection for service and commissioning and firmware download 

 
LED indication 

 

LED 

Color 

Activity 

Function 

Run 

Green  Steady ON 

Device is ready for operation 

Steady OFF 

Device is not powered 

Regular flashing 

Start-up or the program is stopped 

Red 

Steady OFF 

OK 

Steady ON 

Program error 
Hardware fault 

Rapid flashing 

Wrong or corrupt software 
No application loaded 

Blinking per wink command 

Physical device identification 

 

 

 

 

Service button (SVC) 
Physical identification on the network. 

Summary of Contents for Desigo DXR1.E02PLZ-112

Page 1: ...tor for buildings with increasing demand on functionality and flexibility in Room Automation VAV applications Combination of compact room automation station and actuator for VAV control No room unit can be connected BACnet IP communications BTL certified 2 port Ethernet switch USB interface Operating voltage AC 24 V Built in 10 Nm actuator Internal 0 500 Pa differential pressure sensor Plug in ter...

Page 2: ... and constant air volume flow control Functions The selected application and its parameters as well as input and output configuration determine the room automation station s functionality A detailed description of functionality is available in the ABT Automation Building Tool online help Communication 2 port Ethernet switch for cost effective cabling via line topology USB connection for service an...

Page 3: ... Single package multiple package 10 Ordering When ordering indicate product number stock number and description Product documentation Topic Title Document ID Installation cable length topology Desigo Room Automation installation guide CM111043 Engineering and commissioning ABT online help N A Installation instruction Mounting instructions A6V11393918 Commissioning Quick guide A6V11526405 Product e...

Page 4: ...ode reader The serial number can be read directly into the engineering tool using a barcode reader Wiring Wiring must be sufficiently insulated to the available rated voltage Sizing and fusing of the wiring depends on the connected load Mounting The automation station is mounted directly on a damper shaft A6V11393929Z02 See the mounting instructions document ID A6V11393918 for detailed information...

Page 5: ... station is maintenance free Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations ...

Page 6: ...0 mm round with centering insert 6 12 8 mm square Minimum shaft length 20 mm Pressure sensor Pressure sensor Measurement range 0 500 Pa Sample rate 500 ms Overload range 0 100 kPa Measuring range accuracy Zero point accuracy Resolution 3 0 2 Pa 12 Bit Connections Interfaces Ethernet Plugs dual RJ45 10M 100M fast Ethernet Interface type IEEE 802 3 compliance Cable type 100M STP CAT 5 USB 2 0 Type M...

Page 7: ...uments can be downloaded from http siemens com bt download FCC regulations Modification of this device to receive cellular radio telephone service signals is prohibited under FCC rules and federal law This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against...

Page 8: ... cause undesired operation General General information Color Light gray Dimensions L W H 137 143 82 mm Weight Net weight 614 1 g Gross weight 817 3 g Diagrams Connection terminals DXR1 E02PLZ 112 Pin Description Terminal 1 2 IP connection USB USB interface 81 82 power 24 V Power supply AC 24 V V System neutral must always be grounded at the transformer ΔP differential pressure detector Connected t...

Page 9: ...9 Siemens A6V11393935_en _c Smart Infrastructure 2020 09 01 Dimensions Dimensions in mm ...

Page 10: ...land Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2019 Technical specifications and availability subject to change without notice Document ID A6V11393935_en _c Edition 2020 09 01 ...

Reviews: