23/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Select communications mode
28 Feb 2009
The zones are defined under
Communication
.
Individual zones can also be disabled via command if they are not being used. This has
the advantage of reducing the load on the bus.
HandyTool
See the parameter in the last column of the following table.
Short name
Basic setting
Parameter
Geogr zone (ap)
–1 (out of service)
*008
Geogr zone (room)
1
*009
Geogr zone (subz)
1
*010
T'swi zone (apartm)
1
*011
TS zone (room)
1
*012
TS zone (subzone)
1
*013
Heat distr zone
–1 (out of service)
*016
Refrig distr zone
–1 (out of service)
*017
Outside temp zone
1
*018
•
Value 0 means broadcast and is thus not allowed.
•
If the geogr zone or a TS zone has value = -1 for one of the three values, the entire
zone is out of service.
ACS
Professional
Reduce bus load
Notes