CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Room operating modes
28 Feb 2009
The following LTE-mode communication object is provided for central control:
Enable Comfort (input)
Possible partner function blocks)
Known partner devices
EnableComfort
Timeswitch zone
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programs to HVAC-Mode Conversion
Siemens:
Synco RMB795
Possible states are:
State
Description
Enabled
Priority 3 influences (
room operating mode
input,
presence detector, room unit) are enabled.
Disabled
Priority 3 influences are disabled.
The effective room operating mode is
Economy.
Comfort
and
Precomfort
are enabled locally in the controller with the following
parameter in the
Room unit
menu on page 114.
Parameter:
Local Comfort mode
Description
HandyTool
Change from
Economy
to
Precomfort
or
Comfort
mode.
*105
Enabled (basic setting)
Precomfort
or
Comfort
can be disabled via the
Enable
Comfort
input.
1
Disabled (ignore
Enable Comfort
input).
Precomfort
or
Comfort
CANNOT be disabled via the
Enable Comfort
input.
0
5.5.3
Central control of room operating mode via
room operating mode input
PPS2
Central
(Synco controller)
Local
1.
2.
3.
DI
DI
3.
Controller
3.
Prio
1.
Central (ACS)
0.
The following LTE mode communication object is used
to control the
room operating mode
from a building
automation and control system:
Room operating mode (input)
Possible partner function blocks)
Known partner devices
HVACMode
Timeswitch zone
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programs to HVAC-Mode Conversion
Siemens:
Synco RMU710 / 20 / 30
RMH760 / RMB795
KNX
R
CO
KNX
R
CO