86/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Control sequences
28 Feb 2009
Select Sequences, Other setpoints:
Select
Sequences
,
Other setpoints:
HandyTool
See the parameters in the last column of the following table.
Parameter for downdraft
compensation
Basic
setting
Range
Resolution
Parameter
HandyTool
Outside temp 0% valve pos
0 °C
–30 … 10 °C
0.5 K
*078
Outside temp max valve pos
–10 °C
–30 … 10 °C
0.5 K
*079
Maximum valve pos
100%
0 ... 100%
1%
*080
The following conditions must be fulfilled:
– The room controller must be in
Comfort
room operating mode.
ETS3
Professional
ACS
Service
Enable the function