29/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Select communication mode
28 Feb 2009
3.3
Implementation of application example
Using the "C3127_Planning and Commissioning Report, Communication Synco 700",
the plant and the required communication settings can be represented in an easy-to-
understand way.
Proceed as follows:
1. Enter general information, such as plant name, device names, device types,
applications, etc.
2. Transfer the device addresses of all bus users and the basic settings of
communication from the floor plan.
3. Enter the "Geographical zone addresses" in agreement with the group formations
made.
The following illustration shows the completed report for the plant of
Sport Ltd:
Possible settings
RMU RMH RMK OZW RMB
RXB QAW
1
2
3
4
5
6
7
Plant
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Room number
309
307
308
308
308
Device name
X
X
X
-
X
X
-
Reception
Conference
Reception
Office
Office
Office
Office
Device type
RMU
7..
RMH,
RMZ
RMK
OZW
771...
RMB
795
RXB
....
QAW
740
RMB795
RXB..
RMB795 [2] RXB..
RXB..
RXB..
RXB..
Plant type
X
X
X
-
X
X
-
B
FC03
FC03
FC03
FC03
FC03
KNX-ID (Example ID: 00FD000016D5)
X
X
X
X
X
X
X
Area [ 0...15 ] . Line [ 1; 2...15 ] .
Device address [1..253;
255
]
X
X
X
X
X
X
X
0.2.10
0.2.114
0.2.110
0.2.111
0.2.112
0.2.113
Decentral bus power supply [ Off,
On
]
X
X
X
-
X
-
-
Aus
Clock time operation [
Autonomous
, Slave, Master ]
X
X
X
X
X
-
-
Autonom
Remote setting chlock slave [ No,
Yes
]
X
X
X
X
X
-
-
Nein
Remote reset of fault [
No
, Yes ]
X
X
X
-
X
-
-
Nein
Geographical zone (Apartment.Room.Subzone)
(A.R.S) [
1
...126 ].[ 1...63 ]. [1]
X
2
2X
X
-
10X
X.X.1
X
1.1.1
1.1.1
2.1.1
2.1.1
2.2.1
2.3.1
2.4.1
(with own room sensor)
X
1
2X
X
-
-
X
X
X
----
X
X
X
Time switch operation [
Autonomous
, Slave, Master ]
X
1
2X
X
-
-
-
-
Time switch slave (apartment) [
1
...126 ] . 1 . 1
X
1
2X
X
-
-
X.1.1
-
1.1.1
2.1.1
2.1.1
2.1.1
2.1.1
Temperature control [
Master
, Slave ]
-
-
-
-
-
X
-
Master
Master
Master
Master
Master
* Control strategy [
Caskade
, Constant, Alternating ]
X
4
-
-
-
-
-
-
** Combination of room control [
Master
,
Slave external setpoint , Slave internal setpoint ]
-
2X
X
-
-
-
-
Room group (name)
-
-
-
-
10X
-
-
Conference
Office
QAW operation zone (apartment) [ ---,
1
...126 ] . 1 . 1
-
-
-
-
10X
-
-
Information
Room /
Room group
Basic settings
Room group Conference
Apartment = 1
Room group Office
Apartment = 2
1
2
3
In agreement with the list created, the settings of the data points with the same names
are to be made on the devices during commissioning.
Procedure for
engineering
Example Sport Ltd
Implementation with
commissioning