44/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Room operating modes
28 Feb 2009
The resultant
Effective room operating mode
is also available as 4 digital
communication objects:
Effective room operating mode Comfort (output communication object)
Effective room operating mode Precomfort (output communication object)
Effective room operating mode Economy (output communication object)
Effective room operating mode Protection (output communication object)
Flags
L S K Ü A
Typ Send
Heartbeat
Zustände
1 0 1 1 0 1.001
DPT_Switch
Ja
0 = Aus
1 = Ein
5.3.8
DESIGO examples
The following are examples of two typical applications of time schedules in conjunction
with local control of the room operating mode.
Rooms with neither a room unit nor a presence detector
The operating mode of Rooms 1 … 3 in a building is determined by the two time
schedules
Building use
and
Room occupancy
. Window contacts are fitted in all rooms.
The following conditions are specified:
•
Overall, the building is in use from 06.00 to 22.00 (
Building use
time schedule).
Outside this period the opening of a window will trip an alarm (2).
•
Rooms 1…3 are used by the same tenant and controlled by the same O
ccupancy
time schedule. Night mode is to operate from 17.00 to 08.00
(Unoccupied)
and the
lunch break is from 12.00 to 13.00
(Standby).
•
In Room 3 the window is opened briefly, once in the morning and once at night (1).
Example 1