59/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Room operating modes
28 Feb 2009
The following LTE-mode communication object is provided for central control:
Enable Comfort (input)
Possible
partner-function
blocks
Known partner devices
EnableComfort
Timeswitch zone
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programme to HVAC-Mode Conversion
Siemens:
Synco RMB795
The states are:
State
Description
Enabled
Priority 3 influences (
RoomOperatingMode,
presence
detector, room unit) are enabled
Disabled
Priority 3 influences are disabled.
The effective room operating mode is
Economy.
Comfort
and
Precomfort
are enabled locally in the controller with the following
parameter in the
Room unit
menu, page 138:
Parameter:
Local comfort mode
Description
HandyTool
Switch from
Economy
to
Precomfort
or
Comfort
mode
*105
Enabled (basic setting)
Means that
Precomfort
or
Comfort
can be disabled via the
Enable Comfort
input.
1
Disabled (ignore
Enable Comfort
input) In this case
Precomfort
or
Comfort
CANNOT be disabled via the
Enable Comfort
input
0
5.5.3
Central control of room operating mode via
Room operating mode
input
PPS2
Central
(Synco controller)
Local
1.
2.
3.
DI
DI
3.
Controller
3.
Prio
1.
Central (ACS)
0.
The following LTE-mode communication object is used
to control the
room operating mode
from a building
automation and control system:
Room operating mode (input)
Possible
partner-function
blocks
Known partner devices
HVACMode
Timeswitch zone
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programme to HVAC-Mode Conversion
Siemens:
Synco RMU710 / 20 / 30
RMH760 / RMB795
KNX
R
CO
KNX
R