87/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05
Building Technologies
Control sequences
28 Feb 2009
Select the valve actuator type from
Sequences
:
HandyTool
Parameter
Short name
Basic setting
*060
Actuator type heating / cooling valve
STP72E (
FNC08: SSP81)
Settings
STE71
1
SSA81
10
Motorized bus
14
STE72 2
SSB81 11
Electromech.
252
STA71 3
SQS81 12
third-party
devices
STP71 4
SSC81 13
Thermal third-party devices
253
STA72E
5
SSP81
14
Motorized third-party devices
254
STP72E 6
With
motorized actuators
(conventional and bus actuators), third-party devices can
also be connected. The actuator running time can be adapted and an offset set
accordingly.
The
offset
considers the time between the electric pulse and the actual mechanic
movement of the actuator. This is especially important for fast running actuators.
For
electromechanic
actuators, the actuator running time can be adapted.
For
fast actuators
, select valve type "Motoric 3rd party devices ".
ACS
Service