RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Control sequences
28 Feb 2009
Select
Sequences
. After selection of third-party devices, a new window opens in which
the heating and cooling runtimes can be set.
Select the actuator runtime from
Sequences
:
HandyTool
See Parameters in the last column of the table below
Motorized and electromechanic valves.
Parameters 4-pipe
Basic setting
Range
Resolution
HandyTool
Running time heating valve
150 s
0 ... 360 s
1 s
*061
Running time cooling valve
150 s
0 ... 360 s
1 s
*062
Offset heating valve
0 s
0 ... 360 s
1 s
*071
Offset cooling valve
0 s
0 ... 360 s
1 s
*072