Control sequences
28 Feb 2009
8.7.1
Parameterizing
Basic functions: see sections 8.1.1 through 8.1.7.
Minimum supply air temperature
and
Maximum supply air temperature
must be
parameterized during engineering.
Select
Edit parameters, Other setpoints
:
Select
Other setpoints.
HandyTool
See Parameters in the last column of the table below
Parameter
Basic
setting
Range
Resolution
HandyTool
parameter
Minimum supply air
temperature
16 °C
10 °C to
Comfort
heating setpoint
0.5 °C
*038
Maximum supply air
temperature
35 °C
Comfort
cooling setpoint to 40 °C
0.5 °C
*039