135/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05
Building Technologies
General and central functions
28 Feb 2009
11.15.2 LTE mode
Enable alarm info
can be operated in LTE mode. Two further types of information are
provided as outputs:
AlarmInfo_CS
and
AlarmText_CS
.
Together with Synco, users do not need to note if the bindings are created
automatically.
Here, the device listens on the bus and sends an alarm when it has highest alarm
priority. This ensures that the management station does not miss any alarms.
AlarmInfo_CS (Output)
Possible partner function blocks
Known partner devices
AlarmInfo_CS
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
AlarmText_CS (Output)
Possible partner function blocks
Known partner devices
AlarmText_CS
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
EnableAlarmInfo (Input)
Possible partner function blocks
Known partner devices
EnableAlarmInfo
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Error code
Short name
4910
RXB room temp. sensor error
4920
RXB room temperature frost
4940
RXB outside temperature frost
4950
RXB el air heater overtemp
4960
RXB general fault
4925
RXB supply air temp sensor error
4970
RXB PPS fault
For more information on the alarm concept, see "Communication on the bus, Synco700
& RXB", CE1P3127.
11.16 Reset the setpoint shift
When the system changes from
Comfort
or
Precomfort
to
Economy
or
Protection
mode
(see page 74), the setpoint shift can be canceled. This function can be enabled and
disabled via
Central functions.
The setpoint adjustment can only be cancelled with the QAX34.1 and QAX84.1 room
units, which have an LCD display. Enabling this function in room units with a
mechanical setpoint adjuster (potentiometer) will cause errors in data transmission.
Display on a Synco
device:
STOP
Note!