144/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
KNX information
28 Feb 2009
13.5 S-mode communication objects for FNC
13.5.1 S-mode input communication objects
Flags:
R
Read
T
Transmit
W
Write
U
Update
C
Communication
)
C.S. = Company-specific
For internal use only
Name
Flags:
Data point type (KONNEX)
Receive
See
R W C T U
timeout
page
Application mode
0 1 1 0 0 20.105 DPT_HVACContrMode
yes
Comfort cooling setpoint
0 1 1 0 0 9.001
DPT_Value_Temp
No
Comfort heating setpoint
0 1 1 0 0 9.001
DPT_Value_Temp
No
Cooling valve override
0 1 1 0 0 8.010
DPT_Percent_V16
No
Damper override
0 1 1 0 0 8.010
DPT_Percent_V16
No
Economy cooling setpoint
0 1 1 0 0 9.001
DPT_Value_Temp
No
Economy heating setpoint
0 1 1 0 0 9.001
DPT_Value_Temp
No
Enable alarm info
0 1 1 0 0 1.003
DPT_Enable
Yes
Enable electric heating
0 1 1 0 0 1.003
DPT_Enable
Yes
Enable fan command value
0 1 1 0 0 1.003
DPT_Enable
No
Fan command value
0 1 1 0 0 5.001
DPT_Scaling
No
H/ C changeover input
0 1 1 0 0 1.100
DPT_Heat/Cool
Yes
Heating surface valve override
0 1 1 0 0 8.010
DPT_Percent_V16
No
Heating valve override
0 1 1 0 0 8.010
DPT_Percent_V16
No
Master/slave HVAC controller
input
0 1 1 0 0 C.S.
1)
13
Byte
Yes
Master/Slave room unit input
0 1 1 0 0 C.S.
1)
4
Byte
Yes
Outside air temperature.
0 1 1 1 1 9.001
DPT_Value_Temp
Yes
Precomfort cooling setpoint
0 1 1 0 0 9.001
DPT_Value_Temp
No
Precomfort heating setpoint
0 1 1 0 0 9.001
DPT_Value_Temp
No
Presence detector input
0 1 1 0 0 1.018
DPT_Occupancy
No
Release dampers
0 1 1 0 0 1.003
DPT_Enable
Yes
Relay Q24
0 1 1 0 0 1.001
DPT_Switch
No
Relay Q34
0 1 1 0 0 1.001
DPT_Switch
No
Return air temperature input
0 1 1 1 1 9.001
DPT_Value_Temp
Yes
Room temperature input
0 1 1 1 1 9.001
DPT_Value_Temp
Yes
Schedule occupancy
0 1 1 0 0 20.003 DPT_OccMode
Yes
Schedule room operating
mode
0 1 1 0 0 20.102 DPT_HVACMode
Yes
Schedule usage
0 1 1 0 0 20.002 DPT_BuildingMode
Yes
Setpoint offset
0 1 1 0 0 9.002
DPT_Value_Tempd
No
Setpoint ... (6 indiv. values)
0 1 1 0 0 9.001
DPT_Value_Temp
No
Setpoints cooling
0 1 1 0 0 222.100 DPT_TempRoomSetpSetF16[3]
No
Setpoints heating
0 1 1 0 0 222.100 DPT_TempRoomSetpSetF16[3]
No
Setpoint shift cooling
0 1 1 0 0 222.101 DPT_TempRoomSetpSetShiftF16[3] Yes
Setpoint shift heating
0 1 1 0 0 222.101 DPT_TempRoomSetpSetShiftF16[3] Yes
Status request
0 1 1 0 0 C.S.
1)
1
Byte
No
Supply air temperature input
0 1 1 1 1 9.001
DPT_Value_Temp
Yes
Temporary Comfort mode
0 1 1 0 0 1.017
DPT_Trigger
No
Triac Y1
0 1 1 0 0 1.001
DPT_Switch
No
Triac
Y2
0 1 1 0 0 1.001
DPT_Switch
No
Triac
Y3
0 1 1 0 0 1.001
DPT_Switch
No
Triac
Y4
0 1 1 0 0 1.001
DPT_Switch
No
Window
switch
input
0 1 1 0 0 1.019
DPT_Window_Door
No