25/52
Siemens
RXB application library (KNX)
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_0
3
Building Technologies
FNC05 – Four-pipe fan coil with electric reheater
30.11.2007
The following parameters are available with application FNC05.
They are set via ETS, ACS, or HandyTool.
Menu
Parameters.
Values/Range
Basic setting
Communication Communication
mode
S-mode / LTE and S-mode
S-mode.
Receive
timeout
0 ... 105 min.
60 min.
Send
heartbeat
0 ... 105 min.
45 min.
Room temperature setpoints
Protection cooling setpoint
10 ... 40 °C
40 °C
Economy cooling setpoint
10 ... 40 °C
35 °C
Precomfort cooling setpoint
10 ... 40 °C
28 °C
Comfort
cooling
setpoint
10 ... 40 °C
24 °C
Comfort
heating
setpoint
10 ... 40 °C
21 °C
Precomfort heating setpoint
10 ... 40 °C
19 °C
Economy heating setpoint
10 ... 40 °C
15 °C
Protection heating setpoint
10 ... 40 °C
12 °C
Sequences
Actuator type heat/cool valve
– STA71
– STA72E
– STE71
– STE72
– STP71
– STP72E
– Electromech 3rd devices
– Thermal 3
rd
devices
– Motorized bus
STP72E
LTE mode Heating outp bus valve
Off/On Off
Cooling outp bus valve
Off/On Off
Motorized and electromechanic Runtime
0 ... 360 s
150 s
Motorized Offset
0 ... 360 s
0 s
Electric heater
– 1-stage
– Mod.
Mod.
Power consumption
0 ... 6500 W
0 W
LTE mode Heating outp bus el heating
Off/On Off
Fan control.
Fan speeds
– External control
– 1-speed/2-speed/3-speed
3-speed
Fan
control.
Manual / Auto
Auto
Minimum on time.
1 ... 10 min
6 min
Temperature sensor B1
– Room
– Return air
– Measured value only
– No sensor
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
90 min (Off)
Periodic fan kick Economy
0 ... 360 min (360min =Off)
360 min (Off)
Fan overrun time
1 ... 10 min
1 min
Room unit
Measured value correction
– 3 ... 3 K
0 K
Setpoint offset range
± 0 ... 10 K
± 3 K
Local
Comfort
mode
Enabled / Disabled
Enabled
Room
unit
Without LCD / with LCD
Without LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Enabled
Temperature
unit
°C or °F
°C
Standard
display
No display / Room
temperature / Setpoint
Room temperature.
Setpoint
display
Absolute / Relative
Relative
General functions.
Digital input 1
Free (bus = 1)
= Contact open/closed
Free (bus = 1)
Occupancy: Occupied
= Contact open/closed
= Contact closed.
Window:
Window open
= Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Free (bus = 1)
Occupancy: Occupied
= Contact open/closed
= Contact closed.
Window:
Window open
= Contact open/closed
Temporary Comfort mode
0 ... 360 min
60 min
On-delay occupancy detector
0 ... 90 min
5 min
Off-delay presence detector
0 ... 90 min
5 min
Central functions
Heating demand signal
Enabled / Disabled
Enabled
Cooling
demand
signal
Enabled / Disabled
Enabled
Boost
heating
Enabled / Disabled
Enabled
Precooling,
free
cooling
Enabled / Disabled
Enabled
Reset setpoint offset
Enabled / Disabled
Disabled
Master/slave Master/slave
Master or slave
Master
Configuration