16/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Definitions / Tools
28 Feb 2009
2.5.3
Major parameterization using room unit QAX34.3
This parameterization mode allows for changing also critical values.
As a worst case scenario, components (controllers/actuators or other plant
parts) may be destroyed.
Start parameterization mode:
•
Press buttons < , > and – simultaneously for about 2 s until the display turns dark.
•
Release the buttons.
•
Press button – twice briefly.
•
Press b and – simultaneously for approx. 2s
Æ
The display goes dark.
•
Press twice briefly.
The display now shows 0 (mode 0).
Use + and / or – to choose between the following modes:
•
0 =
Normal mode (normal room unit functions).
•
1 =
•
2 =
Display mode (see 2.5.2).
•
3 =
Parameterization mode (see 2.5.2).
•
4 =
Upload (see 2.6).
•
5 =
Download (see 2.6).
•
6 =
Service mode:
All parameters can be set.
They are displayed with prefix "S", e.g. S053.
Press +/– to find the number and confirm with < (Enter).
This displays the corresponding value.
Press +/– to change the value and confirm with < (Enter).
Press > (Escape) to return to the selection without changing anything.
Press Escape again to return to the mode selection.
Press Escape again to return to Normal mode (room unit).
A list of the parameters by number and in alphabetical order is located in chapters 12.7
and 12.8, and in the description of the functions.
A table of parameters with enumerations fort he HandyTool is shown in Section 12.9.
2.5.4
Select the device address using room unit QAX34.3
The device address is contained in parameters *001, *002 und *003.
*001 can assume the values 0 … 15.
*002 can assume the values 0 … 15.
*003 can assume the values 1 … 255.
Example: 0.2.27
Each address must be unique within a plant.