84/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Control sequences
28 Feb 2009
Select
Sequences
.
HandyTool
See the parameters in the last column of the following table.
Short name
Range
Basic setting
HandyTool
Heat surf bus valve
0 = Disabled / Off,
1 = Enabled / On
Disabled (0)
*086
8.1.3
Valve exercising feature
To prevent valves from seizing after long periods of inactivity (e.g. cooling valve in
winter), the valves are operated from time to time. The valve actuators are operated in
such a way as to waste as little heating or cooling energy as possible.
The valve exercising function is triggered if the valve has been closed for ca. 91 hours
without interruption.
8.1.4
Override radiator valve actuators
For test purposes, the valve actuators can be overridden via the following
communication object:
Heating surface valve override (input communication object)
Flags
R W C T U
Type Receive
timeout
Value
0 1 1 0 0 8.010
DPT_Percent_V16
No
0...100%
0 = 0%
+100 = +100%
+32767 = invalid
To override the radiator valve actuator, the test mode must be activated via the
communication object
Application mode
(see page 105).
ACS
Service
KNX
R
CO