RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Master/slave
28 Feb 2009
•
The M/S function presupposes that all 3 M/S zones match.
•
If the master/slave function is not required, the M/S zone should be disabled (to limit
the load on the bus).
HandyTool
Parameter Short
name
Basic setting
*021
Master/Slave
Master
*022
M/S zone (apartm)
1
*023
M/S zone (room)
–1 (out of service)
*024
M/S zone (subzone)
1
Parameter Setting
HandyTool
*021
Master/Slave
Master
1
Slave
0
9.2.1
Window switch (LTE mode)
For master/slave mode, only the master's window switch is evaluated without special
measures, which also influences the slave controllers.
Window switches on the slaves are NOT considered.
9.2.2
Presence detector (LTE mode)
For master/slave mode, only the master's presence detector is evaluated without
special measures, which also influences the slave controllers.
Presence detectors on the slaves are NOT considered.
9.2.3
Dewpoint sensor (LTE mode)
For master/slave mode, only the master's presence detector is evaluated without
special measures, which also influences the slave controllers.
Window switches on the slaves are NOT considered.