112/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
General / central functions
28 Feb 2009
10.15.2 KNX signals on digital/analog outputs
Y1
RXB... Room controller
Triac Y1
10384Z22en
Triac Y1 (input communication object)
Triac Y2 (input communication object)
Triac Y3 (input communication object)
Triac Y4 (input communication object)
Flags
R W C T U
Type Receive
timeout
States
0 1 1 0 0
1.001
DPT_Switch
No
0 = Off (no voltage)
1 = On (AC 24V)
10.15.3 Mapping the sensor B1 to the Konnex bus
B1
RXB... Room controller
Analog input B1
10385Z201en
Sensor B1 can be set on the bus in S-mode as universal temperature (e.g. outside
temperature). To do this, the temperature sensor must be parameterized as
"measurement only“ (see page 74.)
Analog input B1 (output communication object)
Flags
R W C T U
Type Send
heartbeat
States
1 0 1 1 0
9.001
DPT_Value_Temp
Yes