115/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Room unit
28 Feb 2009
The measured value of the integrated temperature sensor can be corrected to
compensate e.g. wall installation issues.
Parameter Basic
setting
Range
Resolution
HandyTool
Measured value correction
0 K
– 3 ... 3 K
0,1 K
*101
This correction is also valid for a sensor that is connected to the analog input B1 (but
not for a bus sensor).
The maximum setpoint shift range is as follows (see also page 72).
Parameter Basic
setting
Range
Resolution
HandyTool
Setpoint offset range
± 3 K
± 0 ... 10 K
1 K
*103
A central station together with communication object
Enable comfort
(see page 57)
can prevent the room operating mode from being more than
Economy
(to save energy).
Enable Comfort
, however, can be ignored in the room controller via the following
parameter:
Parameter Description
HandyTool
Local Comfort mode
Change from
Economy
to
Precomfort
or
Comfort
mode.
*105
Enabled (basic setting)
Precomfort
or
Comfort
can be disabled via the
Enable
Comfort
input.
1
Disabled (ignore
Enable Comfort
input).
Precomfort
or
Comfort
CANNOT be disabled via the
Enable Comfort
input.
0
You can choose whether or not the room unit has an LCD display. If yes, the following
parameters can also be set.
Beim HandyTool ist fix "Mit LCD" eingestellt.
Parameter Description
Basic
setting
Room unit
Without LCD / with LCD
Without LCD
The display of the heating and cooling symbols can be enabled or disabled. Note that
this applies only to room units with an LCD display.
Symbols:
Cooling sequence active
Heating sequence active
Parameter
Description
Basic setting
Show heating/cooling symbols
Displays heating and cooling symbols.
Enabled
The room temperature can be displayed either in Celsius (°C) or Fahrenheit (°F). Note
that this applies only to room units with an LCD display.
Parameter Value
HandyTool
Temperature unit
(Only room units with LCD).
*108
Celsius (°C) (basic setting).
1
Fahrenheit (°F)
0
Sensor correction
Note
Setpoint shift range
Local Comfort mode
(LTE mode only)
Room unit
Display heating and
cooling symbols
(ETS only)
Select temperature unit