25/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Select communication mode
28 Feb 2009
The zones are defined under
Communication
.
Individual zones can also be disabled via "Command" if they are not being used. This
has the advantage of reducing the load on the bus.
HandyTool
See Parameters in the last column of the table below
Short description
Basic setting
Parameter
Geographical zone (apartment)
– 1 (out of service)
*008
Geographical zone (room)
1
*009
Geographical zone (subzone)
1
*010
Time switch zone (apartment)
1
*011
Time switch zone (room)
1
*012
Time switch zone (subzone)
1
*013
Heat distr zone heating coil
– 1 (out of service)
*014
Heat distr zone cooling coil
– 1 (out of service)
*015
Heat distr zone heating surface
– 1 (out of service)
*016
Outside temperature zone
1
*018
•
Value 0 means broadcast and is therefore prohibited.
•
If in the Geogr. zone or in the Time switch zone one of the values is = –1, the entire
zone is "Out of service".
ACS
Professional
Reducing the bus load
Notes