FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05
Building Technologies
Control sequences
28 Feb 2009
Select the damper actuator runtime from
Sequences
:
HandyTool
See Parameters in the last column of the table below
Parameter name
Basic setting
Range
Resolution
Parameter
Running time damper heating
150 s
0 ... 360 s 1 s
*061
Running time damper cooling
150 s
0 ... 360 s 1 s
*062
Changeover time damper
0 s
0 ... 360 s 1 s
*070
8.2.2
Value representing damper actuator positions
The position value for the damper actuator is mapped to the same communication
objects as the heating coil /cooling coil valve position (see page 89):
Heating coil output
and cooling coil output
.
The value is the same on both communication objects,
i.e. the previously
determined damper stroke:
e.g. 0 ... 40% damper stroke is equivalent to cooling from 100 …0%.
41 ... 54% damper stroke = neutral zone.
55 ... 100% damper stroke is equivalent to heating from 0 …100%.
Heating coil output (Output communication object)
Cooling coil output (Output communication object)
Flags
R W C T U
Type Send
heartbeat
Value
1 0 1 1 0 5.001
DPT_Scaling
yes
0...100%
0 = 0%
255 = 100%