RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Control sequences
28 Feb 2009
8.2.3
Overriding the damper actuator
For test purposes, the damper actuator can be overridden via the following
communication objects:
Damper override (Input communication object)
Flags
R W K T U
Type Receive
timeout
Value
0 1 1 0 0 8.010
DPT_Percent_V16
no
0...100%
0 = 0%
+100 = +100%
+32767 = invalid
Before the damper actuator can be overridden, “Test” mode must be activated via the
communication object
Application mode
(see page 128).
The actuator is operated in accordance with the settings shown below:
Heating
value
Cooling
value
Control
Invalid Invalid -----
Valid
Invalid Heating
Invalid
Valid
Cooling
Valid
Valid
The full travel of the damper is 0…100%.
The actuator moves to the position defined by the
heating value.
KNX
R
CO
Note