Installation guide RXB, RXL
CM110381en_01
Building Technologies
Konnex bus technology
28 Feb 2009
We recommend the Siemens IP router, ordering:
•
5WG1 146-1AB01, short description N146
Bus connection via bus terminals, IP network connection via RJ45 plug
Additional information is available in the product and function description (including
with each device) or at:
For large plants with Synco, use Siemens IP routers as of version R4 (stamped
R4), since only these IP routers contain the LTE filter worksheet (see Section
4.5.8.2).
4.5.8
Filter worksheets
4.5.8.1 S-mode
filter
worksheet
The filter worksheet for plants, working in S-mode, are automatically calculated by
the ETS (EIB Tool software) and can then be loaded to the coupler.
4.5.8.2 LTE mode filter worksheets (predefined)
It responds differently in the LTE mode. Filter worksheets for the zone are
predefined in the couplers. The zones must be assigned accordingly during
engineering.
Relevant zone are predefined for RXB / RXL
LTE telegrams with the following
zone addresses are…
Zones
locked forwarded
Geographical zone (apartment)
1 … 110
111 … 126
Timer zone (apartment)
1 … 110
111 … 126
Master/Slave zones (apartment)
1 … 110
111 … 126
Heat distribution zones
1 … 15
16 … 31
Refrigeration distribution zones
1 … 15
16 … 31
Outside temperature zone
1 … 15
16 … 31
For more information on Synco and LTE mode, see CE1P3127