13 / 20
Siemens
RXZ95.1/LON – Gateway EnOcean/LonWorks
CM2N1661en_02
Building Technologies
Workflow with RXT10 and SBT generic plug-in
23 Sep 2011
Step
Procedure
7
Configure the gateway:
Select
Sensor Object [0...8]
…SCPT
max/min
Rnge
:
Measuring range of temperature sensor
[0...40
C, default]
SCPTmaxSendTime
:
Sending interval L
ON
W
ORKS
Recommendation: Same as RXC
Default
2700 [s]
(45min)
8
> Close > Active Plug-in finish
Network
>
Disconnect
(Attached offnet)
9
Make RXT10 bindings:
Datapoint
Gateway
RXC
Room Temperature:
nvoHVACTemp_x
nviSpaceTemp
Setpoint Offnet:
nvoSetpoint_x
nviSetpointOffset
10
Netwok > Connect
(online)
11
Assign
devices
and
install
12
Device > Configure > OK