14 / 20
Siemens
RXZ95.1/LON – Gateway EnOcean/LonWorks
CM2N1661en_02
Building Technologies
Workflow with RXT10 and SBT generic plug-in
23 Sep 2011
Step
Procedure
13
Learn-in the room unit:
Select
Sensor Object [0...8]
Double click
nviLearn
> Set Bit [0] = 1 to learn-in Sensor [0]
> Press button on the room unit
When the learn telegram is received, bit [0] is automatically reset.
Additional room units: Repeat procedure
set bit [1] = 1 to learn-in Sensor [1]
set bit [2] = 1 to learn-in Sensor [2]
etc.