5 / 20
Siemens
RXZ95.1/LON – Gateway EnOcean/LonWorks
CM2N1661en_02
Building Technologies
Workflow with RXT10 and LNS plug-in
23 Sep 2011
Workflow with RXT10 and LNS plug-in
Basis:
PC with DESIGO infrastructure
RXT10 version 4 or higher
Note:
The following components must be installed in the order indicated.
Step 1:
Installation of L
ON
M
ARK
resource files version 13.00 or higher
Source:
Step 2:
Installation of device resource files:
Source:
Download from the DESIGO RX intranet:
Step 3:
Installation of SRC04-FTT plug-in
Source:
Download from the DESIGO RX intranet:
Set up the gateway with the RXT10 tool by following the standard procedure for
integration of third-party devices (for details, refer to User Manual RXT10,
CM110669).
Step
Procedure
1
Device
>
Add
Select tab
Device Type
.
From menu
Device Type
, select
PLG: Plug In Support
.
On the "Device" list, highlight
PlugInDevice
.
2
Select tab
Overview
and enter the location.
Confirm by clicking
OK
.
Infrastructure
Engineering with
RXT10 and
LNS plug-in