background image

Selection Table 1: Direct-On-Line Starters

Motor

Output

at 415V,

3ph, 50Hz

I(fl) 

4 Pole
motor

Size

DOL Starters

Contactor

Recommended Over-load

Relay 50°C

Recommended Fuse-

Switch

Recommended

Cu cable size

Type Reference

1)

Type Reference

1)

Type

Range

Type

Max. Backup

HRC Fuse

Rating

(kW/HP)

(A)

(A)

(A)

(mm

2

)

11/15

20.8

DOL-1

3TW7493-2A..

3TS3400-0A..

3US5200-2C8K

16-25

3KL815

50

6

15/20

28

DOL-2

3TW7494-2A..

3TS3522-0A..

3US5600-2D8K

20-32

3KL815

50

6

18.5/25

34

3TW7495-2A..

3TS3622-0A..

3US5600-2Q8K

25-36

3KL815

63

10

22/30

40

DOL-3

3TW7496-2A..

3TS4722-0A..

3US5800-2F8K

32-50

3KL821

80

16

30/40

53

3TW7497-2A..

3TS4822-0A..

3US5800-2T8K

40-57

3KL821

100

16

37/50

65

3TW7498-2A..

3TS4822-0A..

3US5800-2V8K

57-70

3KL822

125

25

45/60

78

DOL-6

3TW7499-2A..

3TS5122-0A..

3US5800-8Y8K

70-95

3KL822

125

35

55/75

96

3TW7590-2A..

3TS5122-0A..

3US5800-5C8K

85-105

3KL823

160

35

1)

 10

th

 and 11

th

 place in the type reference is for coil voltage code, refer Table 3.

Selection Table 2: Automatic Star-Delta Starters

Motor

Output

at 415V,

3ph, 

50Hz

I(fl) 

4 Pole
motor

line

current

I(fl) 

4 Pole
motor
phase

current

Size

ASD Starters

Contactor

Main

Contactor

Star

Contactor

Delta

Recommended  

Over-load Relay 50°C

Recommended  

Fuse-Switch

Recommended  

Cu cable size

Type  

Reference

1)

Type  

Reference

1)

Type  

Reference

1)

Type  

Reference

1)

Type

Range

Type

Max. 

Backup

HRC Fuse

Rating

Incoming

(from

supply)

Outgoing

(to  

motor)

(kW/HP)

(A)

(A)

(A)

(mm

2

)

(mm

2

)

22/30

40

23.2

ASD-2

3TE7493-2A… 3TS3522-0A.. 3TS3511-0A.. 3TS3511-0A.. 3US56 00-2C8K 16-25 3KL815

50

16

10

30/40 

53 

30.6 

3TE7494-2A…  3TS3522-0A.. 3TS3511-0A.. 3TS3511-0A.. 3US56 00-2D8K 20-32 3KL815

63

16

10

37/50

65

37.5

3TE7495-2A… 3TS3622-0A.. 3TS3511-0A.. 3TS3611-0A.. 3US56 00-2R8K 32-40 3KL821

80

16

10

45/60

78

45

ASD-3

3TE7496-2A… 3TS4722-0A.. 3TS3522-0A.. 3TS4722-0A.. 3US58 00-2F8K 32-50 3KL821

100

35

16

55/75

96

55.4

3TE7497-2A… 3TS4822-0A.. 3TS3522-0A.. 3TS4822-0A.. 3US58 00-2T8K 40-57 3KL821

100

35

25

1)

 10

th

 and 11

th

 place in the type reference is for coil voltage code, refer Table 3.

4

Selection Table 3

Coil Voltage

10

th

 - 11

th

 digit in MLFB

24V

B0

110V

F0

230V 

P0

240V 

U0

415V 

R0

All other voltages

Upon enquiry

Selection Table 4

Star-Delta Timer

Input Voltage

MLFB

24/100 - 127V

3RP1576-1NQ308K

200 - 240V

3RP1576-1NM208K

380 - 440V

3RP1576-1NM208K

Timer  to  be  selected  according  to  contactor  coil  voltage.

Spares List

Type of spares

MLFB

ON/OFF Actuator 

3SX155-21YA

ON/OFF Contact (DOL 2 & ASD 2)

3SX155-11YA

Reset cord for ASD3

3UX1015

Accessory for 3US58 independent 
mounting

3UX1421

Contact Block (1NO)

3SB5420-0B

Contact Block (1NC)

3SB5420-0C

Contactor Spare Contact Kit

Refer Siemens Price List

Electronic Star-Delta Timer

Refer Table 4

Relay 

Refer Table 1 & 2

Contactor 

Refer Table 1 & 2

Aux. contact block for 3TS34

3TX4010-2A

Tightening Torque

DOL 

& ASD 

Starter

Incoming 

terminal

Tightening 

Torque

Outgoing 

Terminal

Tightening 

Torque

DOL 1

M4

1.0-1.5Nm

M4

1.0-1.5 Nm

DOL 2 

M4 

1.0-1.5 Nm 

M5 

2.5-3.0 Nm

DOL 3 

M6 

3.0-4.0 Nm 

M5 

2.5-3.0 Nm

DOL 6 

M6 

3.0-4.0 Nm 

M5 

2.5-3.0 Nm

ASD 2 

M4 

1.0-1.5 Nm 

M4 

1.0-1.5 Nm

ASD 3 

M6 

3.0-4.0 Nm 

M6 

3.0-4.0 Nm

Cover  fixing  torque  1.5-2.1Nm.

40

Summary of Contents for DOL Series

Page 1: ...on as you open the starter you will see a sticker K1 BIRELAY showing the location at which the relay should be mounted Refer Table 5 for the procedure to be followed for fitting the relay Complete the wiring by connecting the wires having ferrules 95 and 96 Wiring should be exactly as per the circuit diagram label shown on inside of the front cover Back up fuse ratings and cable sizes are also rec...

Page 2: ...rrent indicated when motor hum reaches a steady pitch c Stop the motor Set timer to this measured value by rotating the dial shown in fig 7 Overload relay setting a For closer protection set the overload relay to actual line current DOL or actual phase current ASD as measured by an Ammeter In the absence of an Ammeter use procedure as given below a Start the motor and let it run for an hour Then g...

Page 3: ...s tripped due to overload In this case you can restart the motor only if you reset it In case you want the starter to be in Self Reset mode the blue knob on relay fig 9 is to be pressed and rotated in anticlockwise direction so that it comes in position A and its edge Fig 8 Starter front view Fig 9 Relay front view Fig 10 Operating characteristics of 3US 5 6 relays Maintenance Keep the interior du...

Page 4: ...2 0A 3TS3511 0A 3TS3511 0A 3US56 00 2C8K 16 25 3KL815 50 16 10 30 40 53 30 6 3TE7494 2A 3TS3522 0A 3TS3511 0A 3TS3511 0A 3US56 00 2D8K 20 32 3KL815 63 16 10 37 50 65 37 5 3TE7495 2A 3TS3622 0A 3TS3511 0A 3TS3611 0A 3US56 00 2R8K 32 40 3KL821 80 16 10 45 60 78 45 ASD 3 3TE7496 2A 3TS4722 0A 3TS3522 0A 3TS4722 0A 3US58 00 2F8K 32 50 3KL821 100 35 16 55 75 96 55 4 3TE7497 2A 3TS4822 0A 3TS3522 0A 3TS...

Page 5: ...ing 3TW7498 2A 3 Loosen the screws of accessory for independent mounting ASD 3 3TE7497 2A 4 Put the relay terminals below the pin type lugs of the cable terminations 5 Hold the relay the way it is shown in the Operating Instructions of terminal carrier and engage the relay hook in the slot of the terminal carrier 6 When the relay edge is flush with terminal carrier edge clamp the relay with termi ...

Page 6: ...DOL 1 2 3TW7493 2A 3TW7494 2A 3TW7495 2A DOL 3 3TW7496 2A 3TW7497 2A 3TW7498 2A DOL 6 3TW7499 2A 3TW7590 2A s Fig 11 Dimensional Details 6 ...

Page 7: ...ASD 2 3TE7493 2A 3TE7494 2A 3TE7495 2A ASD 3 3TE7496 2A 3TE7497 2A 7 ...

Page 8: ... recycling through authorised dealer Because of the long lifetime of Siemens products the disposal guidelines may be replaced by other national regulations when taking the product out of service The local customer care service is available at any time to answer disposal related questions Siemens Products are environment friendly which predominantly consist of recyclable materials For disposal we r...

Reviews: