Commissioning and diagnostics
ECOFAST Motor Starters
4-8
GWA 4NEB 950 5221-12 DS 01
Additional responses
In addition, the following responses are triggered:
• The switching elements and the brake output are deactivated.
• In the process image, DI-0.0 "Ready (automatic)" is deleted.
Restarting after internal tripping in the device
If the motor starter deactivates the switching elements automatically, it will
not restart until the following have occurred:
• Cause eliminated
• Acknowledgement issued
Acknowledgement
You can acknowledge in the following ways:
• With "Trip reset"
– output DO-0.3
"Trip reset" via fieldbus
• With a counter-command, e.g. "Motor off" (only in the case of a process
image fault)
• Automatic acknowledgement depending on parameter PO-0.3 "Auto reset"
(only in the case of temperature sensor faults)
Attention
If trip reset is applied constantly, the acknowledgement is triggered once by
edge triggering.
If trip reset (output DO-0.3) is applied for longer than 2 seconds and there is
no general fault/general warning present, the self-test function is triggered.
This results in overload tripping with "Warn/Trip", depending on the
"Behavior in the event of overload - temperature sensor" parameter (PO-0.2).
Trigger trip reset (delete signaling bits)
Signal result and enter in
500 ms
> 10 ms
diagnosis buffer
Summary of Contents for Ecofast 3RK1 323-2AS54-1AA0
Page 1: ...Motor Starter Manual 03 2007 ecofast Totally Integrated Automation ...
Page 2: ......
Page 12: ...ECOFAST Motor Starters viii GWA 4NEB 950 5221 12 DS 01 ...
Page 40: ...Installation of Motor Starters ECOFAST Motor Starters 3 8 GWA 4NEB 950 5221 12 DS 01 ...
Page 58: ...Device functions ECOFAST Motor Starters 6 6 GWA 4NEB 950 5221 12 DS 01 ...
Page 74: ...ECOFAST Motor Starters GWA 4NEB 950 5221 12 DS 01 ...
Page 75: ......