Installation of Motor Starters
ECOFAST Motor Starters
GWA 4NEB 950 5221-12 DS 02
3-7
Deutsc
h
En
glish
4
Connect the AS-i cables in accordance in the diagram below:
Attention
If the motor starter is the last station on the AS-Interface line, you must
terminate the ends of the AS-i cables with cable end covers
(Order No.: 3RK1901-1MN00) in order to obtain degree of protection IP65. To
allow this, leave the cable ends projecting by about 10 cm beyond the AS-inter-
face.
5
Connect the motor starter and motor with the motor connecting cable.
Secure the connections with the locking devices.
6
Connect the data lines to the data tee connector.
Secure the connection with the locking device.
7
Connect the terminating connector to the last load feeder (non-assigned con-
nection on the last data tee connector).
Secure the connections with the locking devices.
Step
Description
Table 3-6: Installation: motor nearby (Forts.)
1
2
3
5
4
AS-i
AUX PWR
3RK1901-1MN00
AS-i
AUX P
WR
Summary of Contents for ecofast 3RK1702-2GB18-0AA1
Page 1: ...Motor Starter Handbuch Manual 04 2009 ecofast Totally Integrated Automation ...
Page 2: ......
Page 12: ...ECOFAST Motorstarter viii GWA 4NEB 950 5221 12 DS 02 ...
Page 40: ...Montage von Motorstartern ECOFAST Motorstarter 3 8 GWA 4NEB 950 5221 12 DS 02 ...
Page 58: ...Gerätefunktionen ECOFAST Motorstarter 6 6 GWA 4NEB 950 5221 12 DS 02 ...
Page 70: ...Bestellnummern ECOFAST Motorstarter C 4 GWA 4NEB 950 5221 12 DS 02 ...
Page 74: ...Korrekturblatt ECOFAST Motorstarter GWA 4NEB 950 5221 12 DS 01 ...
Page 84: ...ECOFAST Motor Starters viii GWA 4NEB 950 5221 12 DS 02 ...
Page 112: ...Installation of Motor Starters ECOFAST Motor Starters 3 8 GWA 4NEB 950 5221 12 DS 02 ...
Page 130: ...Device functions ECOFAST Motor Starters 6 6 GWA 4NEB 950 5221 12 DS 02 ...
Page 138: ...Technical data ECOFAST Motor Starters A 8 GWA 4NEB 950 5221 12 DS 02 ...
Page 146: ...ECOFAST Motor Starters GWA 4NEB 950 5221 12 DS 02 ...
Page 149: ......