MicroHarmony Cell Sizes 40 - 260A Manual
Electrical Description
19001467: Version 1.0
4-1
s
4
4.1 Ratings and Performance
All ratings at Tamb
≤
40 °C at 180CFM, 0.95 output power factor for the 40-140A cells.
All ratings at Tamb
≤
40
°C at 300CFM, 0.95 output power factor for the 200-260A cells.
1.
Maximum continuous steady state output current rating.
2.
Output Current Rating of cell with 110% output current for 1 minute out of every 10 minutes.
3.
Output Current Rating of cell with 150% output current for 1 minute out of every 10 minutes.
4.
Output Current Rating of cell with 200% output current for 3 seconds out of every 10 minutes.
5.
Average nuisance out of saturation trip current. The IGBTs and Out of Saturation sense circuit on the cell
control board will trigger a fault at or above this output current.
CHAPTER
4
Electrical Description
10000424.
040
070
100
140
10000494
.200
10000492
.260
Rated Output Current Rating
1
40Arms
70Arms
100Arms
140Arms
200Arms
260Arms
110% 1min/10min (CL-1)
2
40Arms
70Arms
100Arms
140Arms
200Arms
260Arms
150% 1min/10min (CL-2)
3
40Arms
70Arms
100Arms
130Arms
200Arms
260Arms
200% 3sec/10min (CL-3)
4
40Arms
70Arms
100Arms
130Arms
200Arms
260Arms
Nuisance OOS Current
5
141Arms
162Arms
198Arms
290Arms
660Arms
970Arms
Base VA Rating (watts)
6
32,360
56,630
80,900
113,260
161,800
210,340
Cell Losses (watts,%)
7
450
1.370%
698
1.217%
944
1.152%
1,139
0.995%
1,640
1.16%
2,160
1.18%
Cell Efficiency
7
98.630%
98.783%
98.848%
99.005%
98.94%
98.82%
Rating Input Current
8
28Arms
48Arms
73Arms
96Arms
140Arms
182Arms
Typical Operational Life, years
9
17.2
20.91
22.19
20.91
17.7
24
Typical Operation Life, years,
10% high line input voltage
10
12.87
15.65
16.61
15.65
13.3
18
Bleed down time, minutes
11
0.84
1.68
2.53
3.37
4.51
6.02
Input Voltage
750Vrms nominal, ±10% (675-825Vrms),
3-phase, 50/60Hz
Rated DC Bus Voltage
1015VDC
Summary of Contents for Eupec
Page 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Page 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Page 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Page 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Page 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Page 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Page 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Page 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Page 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Page 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...