This section summarizes the Siemens Harmony VFD message protocol and data handling between the Host and Cell
Control Boards (CCB). The scope of this document includes a detailed description of the actual message contents and
the CCB's implementation.
11.1 Operating Modes
The Harmony CCB supports 4 message modes where one of these modes is dedicated for normal power cell
operation. The remaining three modes are dedicated for cell diagnostic and test purposes. Each of these
communication modes are fully defined in Appendix B of this document.
11.2 Reference Documents
11.3 Fiber Optic Message Protocol
The Master Link to CCB communication link is based on a pair of “FOLA” (SGS-Thomson IMS C011 cloned in
mode “0”) transceivers that operate in a Master/Slave mode. The Modulator Card serves as the master and the CCB is
the slave device. This means that the CCB only generates a message in response to receipt of a complete message
packet from the Modulator. If no message is received, the CCB does not transmit any messages. This fact in turn
causes all cells to be shut down. Any communication failures detected by the Modulator also cause a drive fault to
occur. Note that this communication link is always active when power is applied to the Harmony VFD. The message
protocol is summarized as follows:
Table 11-1: Host/CCB Communication Protocol
CHAPTER
11
Communication Protocol
Description
Part Number
Siemens Cell Control Board Schematic
TBD
Siemens Cell Control Board GAL (U31) Logic
TBD
Siemens FOLA
TBD
Transceiver
Inmos IMS C011
(from SGS-Thomson)
Message/Data Size
7 bit data + 1 parity bit
Parity
Odd
Data Rate
5 M baud
Message Rate
9 - 11 microsecond update
Slave Response Time
Initiated approximately 1.2 micro-
seconds after receipt of Link to
CCB message
Protocol
Per TR-xxxxx
Summary of Contents for Eupec
Page 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Page 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Page 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Page 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Page 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Page 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Page 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Page 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Page 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Page 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...