Communication Protocol
MicroHarmony Cell Sizes 40 - 260A Manual
11-8
19001467: Version 1.0
s
11
11.10 Mode 11 Data
11.10.1 Modulator to CCB
Mode 11 is dedicated, for the purpose of diagnostics, to provide a means to test device status. It also provides an
indication if the Cell bypass option is available.
Table 11-11: Mode 11 Modulator to CCB Data
11.11 Device Testing
In order to determine operational integrity of the Power cells, the status of each power switching device and bypass
components can be tested via Mode 11. In the case of Perfect Harmony Next Gen Control, cell bypass is not
available, so the bypass tests are not performed. These device tests are controlled by the Harmony microprocessor
and are performed one device at a time (and one cell at a time) where switching and bypass tests are not performed if
any blocking failures are detected.
11.11.1 Device Test Control Data
Table 11-12: Mode 11 Device Test Control Data
Bit
Description
0
1 -> Mode definition bit
1
1 -> Mode definition bit 1
2
Enable Device Testing
3
Device Test A (Least Significant Bit)
4
Device Test B (Most Significant Bit)
5
Not Device Test Enable
6
Sync pulse for temperature engine
7
Odd Parity Bit
Test
Bit 2
Bit 3
Bit 4
Bit 5
All Devices Blocking
1
1
1
1
Q1 Switching
0
1
1
1
Q2 Switching
1
0
1
1
Q3 Switching
1
1
0
1
Q4 Switching
1
1
1
0
Bypass (using Q1)
0
0
0
1
Bypass (using Q2)
0
1
0
1
Summary of Contents for Eupec
Page 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Page 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Page 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Page 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Page 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Page 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Page 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Page 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Page 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Page 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...