MicroHarmony Cell Sizes 40 - 260A Manual
Testing
19001467: Version 1.0
7-1
s
7
7.1 Documents for Testing Cells
The following ISO documents should be used for testing cells:
•
TSI-062 must be followed for testing.
•
TSI-063 must be followed for repair testing.
•
TSF-058 includes cell ratings and test parameters.
•
QSI-013, section 4.3.4 includes instructions for product identification and traceability.
7.2 Testing Equipment
MicroHarmony cells can be tested on Siemens Automated Cell Tester or manually. If tested manually, the following
equipment is required.
1.
Cell Tester P/N 469939.00.
2.
Load inductors P/N 161661.13 (2mH in parallel, 8mH in series) or a suitable equivalent with required
minimum inductance and current specification (see following table).
3.
Variable voltage source (Variac) with a voltage range of at least 0-500Vrms 50/60Hz, with at least 30Arms
secondary rating.
4.
Step-up transformer 480:720Vrms minimum rating, with at least a 2kVA rating. P/N 164307.00 is
recommended.
5.
Alternatively, the step-up transformer can be eliminated if a variac capable of at least 750Vrms secondary is
available.
6.
IBM 286 or greater with Centronics port and EGA capability.
7.
Clamp on Ammeter (Beckman CT-232 or equivalent).
8.
DVM capable of measuring up to 1500Vrms.
7.3 Required Tests
•
Inspection/ Ohm Check
•
HIPOT Test
•
Rectifier Test
•
Preliminary Cell Tests
•
Thermistor Burn-In Test
•
Burn-In Test
•
Diagnostic Display Check
CHAPTER
7
Testing
Summary of Contents for Eupec
Page 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Page 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Page 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Page 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Page 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Page 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Page 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Page 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Page 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Page 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...