4
Planning
Operating modes
40
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
4.2.1
Parameter Sets
The following information applies to the 'Automatic: switches between blue and
blue-red based on ratio' mode.
FDA241
Set
No.
Sensitivity [%/m]
Comment
Inspect
Prealarm Fire 1
Fire 2
0
0.07
0.10
0.15
20
default
1
0.03
0.04
0.05
2
-
2
0.03
0.045
0.06
2.5
-
3
0.04
0.055
0.07
3
-
4
0.05
0.075
0.10
4
-
5
0.07
0.10
0.15
5
-
6
0.08
0.14
0.20
6
-
7
0.18
0.28
0.40
8
-
8
0.30
0.50
0.70
10
-
9
0.40
0.70
1.00
15
-
10
0.80
1.40
2.00
20
-
FDA221
Set no.
Sensitivity [%/m]
Comment
Prealarm
Fire 1
Fire 2
0
0.50
0.70
20
default
6
0.14
0.20
6
-
7
0.28
0.40
8
-
8
0.50
0.70
10
-
9
0.70
1.00
15
-
10
1.40
2.00
20
-