7
Commissioning
Operation on addressed detector line
80
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
Selection of settings
Field
Action
Purge activation mode
Select the purge interval
You can choose from the following:
Off
Auto max. 1x
Auto max. 2x
Auto max. 3x
Interval 12 h
Interval 1 week
Inteval 1 month
Interval 4 months
Purge cycle duration
Set purge duration
You can choose from the following:
20 s (default)
5 s
10 s
15 s
30 s
40 s
60 s
Airflow error delay time
Set the time delay for airflow faults.
You can choose from the following:
15 sec
60 sec
120 sec
300 sec
Airflow supervision window
Set tolerances for airflow faults.
You can choose from the following:
±20%
(±30%)
(±50%)
(±80%)
Detector mode
Evaluation levels for detection.
You can choose from the following:
Automatic: switches between blue and blue-red based on
ratio
Robust
Ultra sense: always blue
Reserved