Building Technologies

A6V10436765_b_en_--

Fire Safety

2014-11-27

“Status” inputs and “Alarm” inputs

“Alarm“ inputs trigger an alarm as soon as the input is activated. “Status“ inputs trigger a
monitoring status change as soon as they are activated.

Line monitoring and circuitry

The input lines are monitored for open line or open/short line. To make these possible,
resistors must be properly connected to the end of lines of the input (Fig.6). When an
open line or a short line occurs on one of the input lines, a trouble message is
transmitted to the control panel.

The input must be potential-free.

Structure

The module consists of the module carrier, the printed circuit board, the cover and the
protection cover. The printed circuit board includes the LEDs. The LEDs indicate the
status of the inputs. The cover of the printed circuit board is transparent, so that the state
of the LEDs is visible even when the housing is closed.

To protect the modules from environmental influences, there are additional options for
the housing.

1

3

4

Fig. 1 Overview

Legend

1.  Input 1

3.   Input 2

2.  Detection line

4.   LED indicator

LED indicator

LED indicator is used for displaying status of input. Each input has an indicator.

Status LED

Meaning

Off

Normal operation

LED flashing every 1 s (250 ms ON)

Input activated

Input 1, LED flashing every 1 s (short flashes)

Localization mode

Summary of Contents for FDCI181-2

Page 1: ...er settings or Dip switch l Power supply via FD18 BUS l Communication with controller via FD18 BUS detection line l Directly used in dry areas Applicable in dusty and humid areas when installed in FDCH221 housing l Sticker Method easy for commissioning Application With the input a status can be monitored the input can be configured by controller or configuration tools as follows l Status input or ...

Page 2: ...e potential free Structure The module consists of the module carrier the printed circuit board the cover and the protection cover The printed circuit board includes the LEDs The LEDs indicate the status of the inputs The cover of the printed circuit board is transparent so that the state of the LEDs is visible even when the housing is closed To protect the modules from environmental influences the...

Page 3: ...oles 182 0 1 0mm 4 Fix and guide in the cables with waterproof joint provided by users themselves 5 Fix the lid additionally with four screws Fig 4 Only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Installation of module in FDCH221 housing Caution Overheating of FDCI1...

Page 4: ... 28 mA Activation current 0 52 mA Monitoring resistors 3 3KΩ 1 4w 680Ω 1 4w Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 Communication protocol FD18 BUS Load factors 3 Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With housing FDCH221 IP65 Approval for Russian TR RF N123 FZ Details for ordering T...

Reviews: