Maintenance / troubleshooting
Adding or removing radio devices
7
41 | 62
Building Technologies
A6V10227639_k_en_--
Fire Safety
2016-11-28
7.4 Adding or removing radio devices
The procedure for adding or removing radio devices on a detector line is no
different to the one used for adding or removing wired devices. The relevant fire
detection system documents also apply to the SWING radio fire detection system.
You will find more information in the 'Changing and expanding the FDnet/C-NET
detector line' chapters of the following documents:
For control panels FC20xx: Document 009052
For control panels FC72x: Document A6V10210416
See also
Connecting the radio gateway [ 29]
Applicable documents [ 7]
7.4.1 Adding radio devices
The procedure for adding radio devices on a detector line is no different to the one
used for adding wired devices. The relevant fire detection system documents also
apply to the SWING radio fire detection system.
Wait until one radio device has been successfully logged on before attempting to
add the next radio device. The internal alarm indicator for the radio device is off.
Figure 17: Radio gateway FDCW241
H2 Yellow LED for maintenance
mode
S1 Button for maintenance mode
H3 Yellow LED for power supply
and reset
S2 Reset button
H4 Yellow LED for radio network
S2
S1
H2
H2
H3
H4