Maintenance / troubleshooting
Adding or removing radio devices
7
43 | 62
Building Technologies
A6V10227639_k_en_--
Fire Safety
2016-11-28
11. Close the radio gateway housing.
12. Switch the detector line on at the station and read in the new radio device in
accordance with the documents for the fire control panel. Note the information
in chapter 'Changing and expanding the FDnet/C-NET detector line' in the fire
detection system documentation.
13. Make a note of the change in your documents.
The new radio device has now been added.
See also
Replacing the batter pack on the radio gateway [ 52]
7.4.2 Removing radio devices temporarily
An individual radio device may be removed temporarily, for example, if renovation
work is being carried out.
WARNING
Risk of injury due to undetected fire
When parts of the system are switched off, they are not monitored and no fire
alarm signals are issued for them.
Keep the amount of time during which parts are switched off to a minimum.
Put the intended safety measures in place.
NOTICE
Do not remove multiple radio devices at the same time
This may cause other radio devices to lose their connection to the radio gateway
and be displayed as missing devices.
When the devices are switched back on, faults may be reported at the station.
Proceed as follows to remove a radio device temporarily:
The radio cell is in normal operation.
1. Remove the radio device by releasing it from the base or housing.
2. Perform the necessary activities.
3. Once the activities are complete, install the radio device in the same base or
the same housing.
The internal alarm indicator flashes.
4. Wait until it has stopped flashing.
The radio device has now been successfully logged on. You can temporarily
remove the next radio device.