Specifications
Technical data
8
54 | 62
Building Technologies
A6V10227639_k_en_--
Fire Safety
2016-11-28
8 Specifications
Unless otherwise mentioned, the following data applies:
Temperature
= 25 °C
Air pressure
= 1000 hPa (750 Torr)
You will find information on approvals on the data sheet for the device.
8.1 Technical data
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document A6V10271323
Detector line
Operating voltage
DC 12…33 V
Operating current
Typ. 1 mA (0.6…25 mA)
Maximum current connection factor 16
Quiescent current connection factor 6
Address connection factor
2 + n*1 (n = number of radio devices)
Separator connector factor
1
Protocol
FDnet/C-NET
Compatibility
See 'List of compatibility'
Design
Inherently short-circuit-proof
Protected against polarity reversal
Protected against overvoltage
Line separator
Line voltage:
Nominal
DC 32 V (= V
nom
)
Minimum
DC 12 V (= V
min
)
Maximum
DC 33 V (= V
max
)
Voltage at which the line separator opens:
Minimum
DC 7.5 V (= V
SO min
)
Maximum
DC 10.5 V (= V
SO max
)
Permanent current when switches
are closed
Max. 1.5 A (= I
C max
)
Switching current (e.g., in the event
of a short-circuit)
Max. 2 A (= I
S max
)
Leakage current when switches are
open
Max. 1 mA (= I
L max
)
Serial impedance when switches are
closed
Max. 0.4 (= Z
C max
)