Mounting/Installation
Electrical connection
5
28 | 42
Building Technologies
A6V10349616_i_en_--
Fire Safety
2019-01-18
5.3 Electrical connection
Notes on work on electrical installations
WARNING
Deactivating the manual call points prevents alarms from being forwarded.
The alarm is not triggered.
●
Mark deactivated manual call points or those which are not fully functional
with the notice 'NOT IN USE'!
Figure 9: 'NOT IN USE' label
WARNING
Connecting cables in environments at risk of explosion
Risk of explosion
●
Only connect cables in an environment that is not at risk of explosion.
If you are permanently decommissioning the equipment, observe the national
regulations governing unused cables in areas at risk of explosion.
Note the positive and negative poles.
Only connect one wire per terminal. This is the only way to ensure the connection
is failure-free for the entire service life of the device.
We recommend that you do not use shielded cables for stub lines in areas at risk
of explosion.
NOT IN USE
AUSSER BETRIEB
HORS SERVICE
FUORI SERVIZIO
FUERA DE SERVICIO
BUITEN GEBRUIK