Specifications
Technical data
8
36 | 42
Building Technologies
A6V10349616_i_en_--
Fire Safety
2019-01-18
8 Specifications
8.1 Technical data
Device labeling
IECEx Scheme:
Ex ia IIC T4 Ga, Ta = -35…70 °C
Ex ia IIIB T135 °C Da , Ta = -35…70 °C
Directive 2014/34/EU:
(ATEX directive)
II 1 G Ex ia IIC T4 Ga, Ta = -35…70 °C
II 1 D Ex ia IIIB T135 °C Da, Ta = -35…70 °C
Ex-related connection
data, intrinsically safe
U
i
28 V
I
i
92 mA
P
i
650 mW
L
i
Negligible
C
i
0,2 nF
Line to external alarm
indicator
U
0
14.2 V
I
0
480 mA
P
0
195 mW
L
0
100 µH
C
0
38 nF
Only for connecting passive, external alarm indicators with
negligibly low inductance and capacitance levels.
You will find an explanation of the formula symbols in chapter 'Technical terms,
abbreviations, and formula symbols [
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
●
Document A6V10349347
Detector line
Operating voltage
DC 13…28 V
Operating current (quiescent)
Typ. 210
μ
A
Maximum current connection factor 1.25
Quiescent current connection factor 1.25
Address connection factor
1
Protocol
FDnet-Ex/C-NET-Ex
System compatibility
See 'List of compatibility'