Specifications
Technical data
8
37 | 42
Building Technologies
A6V10349616_i_en_--
Fire Safety
2019-01-18
External alarm indicators
Number of external alarm indicators
that can be connected
Max. 1 external alarm indicator FDAI9x-Ex
Voltage
DC 9…14.2 V
Current
9…15 mA
Length of line
●
Max. 30 m with unshielded cables, or
when the shielding is connected to the
positive pole of the detector base
●
Max. 5 m, if the shielding is connected
to earth
Flashing interval times:
●
Bright
12 ms
●
Dark
1 s
Connections
Detector line and external alarm
indicators:
●
Design
Spring clips
●
Conductor cross section
1…1.5 mm²
Ambient conditions
Operating temperature
-25…+70 °C
Storage temperature
-35…+75 °C
Air humidity
≤
95 % rel.
Protection categories (IEC 60529):
●
Manual call point
IP44
●
Manual call point with seal
DMZ1197-AD (accessories)
IP66
Environmental category according to
EN 54-11
In buildings and outdoor areas
Electromagnetic compatibility:
●
1 MHz…1 GHz
50 V/m
●
1 GHz…2 GHz
30 V/m
Mechanical data
Design according to EN 54-11
Type B (indirect activation)
Dimensions (W x H x D)
134 x 134 x 43 mm
Housing material
Polyamide (PA)
Color
~RAL 3000 flame red
Weights:
●
Housing
0.302 kg
●
Switching unit
0.071 kg
●
Glass insert
0.011 kg
●
Protective cover
0.012 kg
Standards
European standards
EN 54-11
International standards
●
IEC/EN 60079-0
●
IEC/EN 60079-11