![background image](http://html.mh-extra.com/html/siemens/fireseeker-fs-100/fireseeker-fs-100_installation-operation-and-maintenance-manual_379173013.webp)
FS-100 Installation & Operation Manual
P/N 315-699461
9
GENERAL SPECIFICATIONS
Operating specifications for the FS-100 are as follows:
Environmental
•
Operating temperature
32 - 120
°
F (0 - 49
°
C)
•
Relative humidity
Up to 85% @ 86
°
F (30
°
C)
Primary Supply
•
Primary Input Voltage: 120 VAC (60 Hz) nominal (FS-100-120)
•
Maximum primary input current: 1.3A at 120 VAC
Secondary and Trouble Power Supply
•
24 volt lead-acid battery set:
•
Maximum Charge Voltage: 27.8 VDC
•
Maximum Charge Current: 1.0 A
•
Maximum Input Current: 3.5A
•
Battery capacity: 7-38 A.H. (over 7 A.H. requires separate enclosure)
Auxiliary Power Outputs
•
Current:
0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards
0.4 amp maximum per power output
•
Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
•
Resettable Power Output
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Status Relays
•
Includes alarm, supervisory and trouble relays.
•
Contact Rating:
1 A, 28 VDC maximum, resistive
•
Form “C” Contact
Notification Appliance Circuits
•
Four Class A, Style Z/Class B, Style Y circuits
•
Power limited
•
Supervised
•
Maximum Standby Current: 3.4mA
•
Alarm Voltage: 24 VDC nominal
•
Maximum Alarm Current per circuit: 1.5 A
•
Total Maximum Alarm Current (all circuits): 2.5 A
•
Maximum Ripple: 16 VAC
•
Maximum Loop Drop Voltage: 1.0 VDC
Technical Manuals Online! - http://www.tech-man.com