BATTERY SIZE CALCULATIONS
Standby Current (A.)
Alarm Current (A.)
FS-100 Control Unit
0.110
0.200
FS-MT Municipal Tie
Module
Standby 0.005
0.005
+
NA
Alarm 0.028
0.028
NA
+
Standby (note 5)
+
NA
Alarm (note 5)
NA
+
FS-232 RS232
Module
Standby 0.008
0.008
+
NA
Alarm 0.008
0.008
NA
+
FS-DACT Module
Standby 0.038
0.038
+
NA
Alarm 0.054
0.054
NA
+
FS-RD Remote
Standby 0.020
X =
+
NA
Annunciator Display
Alarm 0.030
X =
NA
+
FS-RU Serial
Standby 0.010
X =
+
NA
Relay Unit
Alarm 0.170
X =
NA
+
FS-RE16 Serial
Standby 0.000
X =
+
NA
Relay Extender
Alarm 0.160
X =
NA
+
FS-SAU Serial
Standby 0.015
X =
+
NA
Annunciator Unit
Alarm (note 4) 0.040 X =
NA
+
FS-SAE16 Serial
Standby 0.005
X =
+
NA
Annunciator Ext.
Alarm (note 4) 0.000 X =
NA
+
Addressable Devices
Catalog #
Quantity
X Current (A.)
Standby
X =
+
NA
Alarm
X =
NA
+
Standby
X =
+
NA
Alarm
X =
NA
+
Standby
X =
+
NA
Alarm
X =
NA
+
Standby
X =
+
NA
Alarm
X =
NA
+
End of Line Relay
Catalog #
Quantity
X Current (A.)
X =
+
+
Notification
Appliances
Catalog #
Quantity
X Current (A.)
X =
NA
+
X =
NA
+
X =
NA
+
X =
NA
+
Other (Aux. DC)
=
+
+
TOTAL