P/N 315-049308-6
2
Step 13.) Connect relay contacts, as required.
Step 14.) Apply power to system.
Step 15.) Program control unit for required relay operation.
Step 16.) Check for proper operation of functions.
FS-RU2 / FS-RE8 WIRING
Notes:
1.)
Units to be installed in accordance with all local codes.
2.)
T-Tapping is not allowed! Communication wiring must be daisy chained from unit to unit.
3.)
Terminal block will accept 12 AWG to 18 AWG wiring.
4.)
Use twisted pair cable with a characteristic impedance of approximately 120 ohms. 4000 feet maximum distance from
end to end.
5.)
Power Limited wiring must be kept separate from non-power limited wiring, ¼ “ minimum.
6.)
All wiring to P2 on the remote processor board must be in the same enclosure.
7.)
The following table gives the currents necessary for power supply and battery calculations.
Model
Standby Current
Alarm Current
Voltage
FS-RU2
0.032 A
0.192 A (All relays activated)
24VDC nominal, filtered
FS-RE8
0.000 A
0.170 A (All relays activated)
24VDC nominal, filtered
FS-RU2 ADDRESS SETTING
Address
Switch 1
Switch 2
Switch 3
Switch 4
1 On On On Off
2 Off On On Off
3 On Off On Off
4 Off Off On Off
5 On On Off Off
6 Off On Off Off
7 On Off Off Off
8 Off Off Off Off
PROCESSOR BOARD HEADER CONNECTIONS
Pin
P2 - Processor Board
1
24V Output (+)
2 Not
Used
3
Lamp Test Switch
4
Alarm Silence Switch
5
Trouble Acknowledge/Silence Switch
6
System Reset Switch
7
Remote Buzzer Output (open collector)
8
Alarm Silence Output (open collector)
9
Trouble Output (open collector)
10
24V Output (-) or GND
SW-1
OFF ON
1
2
3
4
Programmable Relay Contacts
(Shown in normal standby condition)
1A@28VDC max., Resistive
For Power Limited Source, Unsupervised
Power Limited, Supervised
Cable for power (+ & -) and Twisted
pair Cable for data (X+ & X-) from
panel or previous remote.
Cable for power (+ & -) and twisted
pair Cable for data (X+ & X-) to next
remote or 120 ohm E.O.L. Resistor
Assembly (P/N 140-050008-1) on the
last remote.
TB3 allows for connection to an
external regulated and power limited
24VDC power supply, listed for fire
protective signaling use.
A = Common (Armature)
C = Normally Closed
O = Normally Open